The Flexy embeds two IO servers dedicated to Mitsubishi PLCs:
- MITSUFX: this IO server allows the Flexy to poll tags on a MITSUBISHI FX series PLC using its serial RS-422 programming connector.
- MELSEC: this IO server allows the Flexy to poll tags on a MITSUBISHI Q series PLC using the MC protocol on the Ethernet interface. It also supports the polling of the FX3U, FX5U and A series over Ethernet protocol.
A summary of the existing situation can be found in the table below:
PLC Model
|
Ethernet
|
Serial |
eWON IO Server |
Comments |
FX series
(except FX3U & FX5U)
|
✘ |
✔ |
MITSUFX |
Polling on serial only. |
Q series
A series
L series
iQ-R series
iQ-F series
FX3U series
FX5U series
|
✔ |
✔ |
MELSEC |
Polling on Ethernet only. |
The remote maintenance functionality is not provided by either IO server. To perform a remote maintenance, the Ethernet routing feature or VCOM feature (serial) of the Flexy must be used.